Jinli DC 1000V PV Surge Suppressor Solar SPD

Basic Info.Model NO.JLSP-GD1000/40TypeSolar SPDStructureZinc Oxide ArresterInstallation Parallel Arrester Application PV System Size Meidum Operation Voltage Low Voltage Shape Cuboid MaterialPBTCertificationROHS, ISO9001, CCC, CeBrandJinliMax. Continuous Operating Voltage UC1200V DCNominal Discharge Current: in 20ka Protection Level up4.0kvMax. Discharge Current: Imax40kaTrademarkJLSPTransport Packageby Sea or by AirSpecification90*36*62OriginChinaHS Code85363000Product DescriptionParameters ModelJLSP-GD1000/40 IEC Classification Class II DC Network Un (50/60Hz)(V)1000/1100V DC Max. continuous operationg voltage Uc (V)1200V DC Nornimal discharge current In (kA)20kA Max. discharge current(8/20us) Imax (kA)40kA Voltage protection level Up (kV)≤4.0kVResponse time tA≤25ns Operating temperature-40°C∼+85°C Relative humidity≤95%(25°C) Max. cross-sectional area of wire25mm2 multi-strand cord Dimensions (1P) (W*L*H) (mm)18X90X62 MountingDIN Rail 35mm Protection ratingIP 20 Housing materialPBT Flame retardant ratingV-0 Capacity of remote signaling contact250VAC/0.5A   30VDC/3A Max.cross-sectional area of wire for remote signaling contact1.5mm2  multi-strand cord/single cord Status indicatorNormal: Green   Malfunction: Red Standards complianceEN50539-11  IEC61643-31  GB/T 18802.31