Description:Double Winding Non-excitation Voltage Regulation
Transformer: Maximum 420000kVA Three Winding Non-excitation Voltage
Regulation Transformer: Maximum 240000kVA Double Winding On-load
Voltage Regulation Transformer: Maximum 240000kVA Three Winding
On-load Voltage Regulation Transformer: Maximum 240000kVA
Autotransformer: Maximum 360000kVA Technical parameters:Name:
Three-phase dual winding with stabilization winding on-load voltage
regulation oil immersion air-cold power transformer Type:
SFZ-120000/230 Rated voltage: 230/34 /25kv Rated capacity:
100000/120000kVA Rated voltage ratio: 230± 8× 1.25%/34kV Rated
current: 301/2038A Phase number: Three Rated frequency: 50 Hz ± 3%
Connection set: Ynyn0(d11) Voltage regulating method: Neutral point
on-load Regulating Short circuit impedance: 9.5%(100MVA) Cooling
mode: ONAN/ONAF Winding insulation level: Lightning impulse
withstand voltage (kVpeak value) 1min Main frequency withstand
voltage (kVRMS) Full wave Chopped wave High voltage side: 1050 1175
460 Neutral point of high voltage: (1050) ( 460 ) Low voltage side:
170 185 70 Neutral point of low voltage: 170 70 Insulation Level: A
Field strength between transformer winding turns is no more than
2kV/mm Transformer loss (under 75) o-load current and efficiency
No-load Loss: 92 kW According to IEC standard Load Loss: 356 kW
According to IEC standard No-load current: 0.3 % According to IEC
standard Radio interference and corona Under the Maximum phase
voltage, corona is not visible from outgoing terminal in the night
of clear day at outdoor. Radio interference voltage is no more than
2500UV. Ratedpower(kVA)ValtageConnction9 loss (kW)10
loss (kW)11 loss (kW)No-load Loss(%)H.V(kV)L.V(kV)No-Load
LossLoad LossNo-Load LossLoad LossNo-Load LossLoad
Loss31500230242±2×2.5%6.36.610.511YNd113513531.5128.328128.30.7400004115736.9149.232.8149.20.7500004918944.1179.639.2179.60.65630005822052.220946.42090.657500010.51113.86725060.3237.553.6237.50.6900007728869.3273.661.6273.60.551200009434584.6327.875.2327.80.55150000112405100.8384.889.6384.80.51600001113.815.751820117425105.3403.893.6403.80.49180000128459115.2436.1102.4436.10.46240000160567144538.7128538.70.42300000189675170.1641.3151.2641.30.38360000217774195.3735.3173.6735.30.3837000015.751820221790198.9750.5176.8750.50.38400000234837210.6795.2187.2795.20.35420000242868217.8824.6193.6824.60.35Provide
users with 500kV and below, 1000MVA and below series oil immersed
power transformers. stay While digesting the advanced technology at
home and abroad, combined with the advanced technology at home and
abroad and our company's experience in producing power transformers
for many years, through Through optimization and innovation, we
have successfully produced a series of power transformers with low
noise, low loss, low partial discharge and high short-circuit
resistance, Fully comply with and superior to national standards
and International Electrotechnical Commission recommended standards
Reference:1. Low loss and low noise The core piece adopts the
laminated form of full oblique joint, and the oil tank adopts
composite shielding technology Structural parts adopt measures such
as reducing eddy current loss to solve the phenomenon of local
overheating. 2. Safe and reliable operation The electrical
calculation adopts simulation software for positioning and
quantitative analysis to ensure sufficient electrical strength and
reliability Low loss and effective suppression of local
overheating; The local discharge is kept below 50pc, and the
temperature rise of transformer winding and oil surface are low
Above 5K of national standard, yield strength of winding conductor
≥ 180n / mm2, copper conductor, transformer It has strong
short-circuit resistance, which can ensure the long-term stable
operation of the transformer. 3. Easy installation and maintenance
The transformer adopts core free structure, and all accessories are
pre installed in the factory. The transformer adopts maintenance
free structure and technology, and the product maintenance is
simple and convenient. 4. Fine workmanship The coil is wound by
vertical winding machine and equipped with tensioning device to
ensure the axial direction of all windings Winding force to improve
the mechanical strength of winding. The combined suit process is
adopted to reduce the assembly tolerance of the body and improve
the overall quality of the body strength. All high voltage
electrodes and metal structures are rounded to avoid tip discharge
Our Best Service For You1.Pre sale servicea.make technical
solutionb.send quotation, technical data sheet and drawingc.prepare
power transmission plan, testing plan and shipment plan2.In sale
servicea.supervise the manufacturing schedule totally in accordance
with the planb.send photos to customer during every manufacturing
process(hold point)c.inform the customer one week before
testing.3.After sale servicea.installation and commissioning,
training the workersb.quick response within 12 h
Related products about 120000kVA 230kv Oil Immersed on Load Tap Changer Power Transformer
- Waste Tyre Plastic Recycling Machinery Machine Tire Crusher Production Line Rubber Crumb Grinding Machine Equipment Tire Shredder
- Stretch Plastic Blowing Pet Bottle Making Blow Molding Machine Bottles Stretch Automatic Pet Bottle Blowing Machine
- Waste Plastic Pet Bottle, Water Bottle Flake, PP/HDPE/LDPE PE Film Jumbo Woven Bags Plastic Crusher Machine, Plastic Crushing Washing Recycling Machine
- Type 2 Wall-Mounted Electric Car Charging Station 7kw /11 Kwelectric Vehicle Charging Station Home Wallbox AC EV Charger Single Phase or 3three Phase
- G-View G12W Wholesale Auto Car LED Headlight Bulb High Power H13 H11 9005 H7 H4 Car LED Headlights LED Car Lights
- New Design Porcelain Round Plates Dinner Set for Wedding and Banquet
- China 2023 New Design Super Soft 100% Polyester Microfiber Knitted Oversized Decoration Hoodie Blanket
- Handmade Art Creative Materials Thickened White Paper Cup DIY Disposable Handmade Colored Paper Cup